Automatic Transfer Switch Control Modules
DSE335
Auto Transfer Switch Control Module
The DSE335 Automatic Transfer Switch Control Module has been expertly developed to monitor the voltage and frequency of an incoming AC supply from two different sources. These sources can be generator or mains (utility), or a combination of both. The control module monitors Source 1 (S1) and Source 2(S2). When a failure occurs a start command is issued to the inactive source to take over the load. The module will return the load to the mains (utility) as soon as this becomes available.
To view UL Certification click here. |
240 mm x 181 mm x 42 mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7” x 6.3”)
MAXIMUM PANEL THICKNESS
8.0mm (0.3”)
WEIGHT
0.9kg
PRODUCT VARIANTS
0335-01 - 335 Auto Transfer Switch Control Module - 12/24 Volt DC Supply
Request a Quote
Product Highlights
Key Features
Key Benefits
- Additional Features
- Passive closed transition.
- 1 Amp & 5 Amp CT secondary support.
- Phase rotation detection.
- Start inhibit.
- Load inhibit.
- Multiple topology support.
- Configurable timers & alarms.
- Multiple date & time scheduler.
- USB connectivity.
- SMS messaging.
- Adjustable MODBUS interframe delay.
- DSEWebNet® compatibility.
- Ethernet communications (with DSE855).
- DSENet® expansion.
- Backed-up real time clock.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
480 mA at 12 V, 360 mA at 24 V
126 mA at 12 V, 96 mA at 24 VS1
S1
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUTS A & E
Normally closed volt-free output
8 A AC at 250 V AC
OUTPUTS B & F
Normally open volt-free output
8 A AC at 250 V AC
OUTPUT C & D
Changeover volt-free output
8 A AC at 250 V AC
AUXILIARY OUTPUTS G,H,I,J,K & L
2 A DC at supply voltage
S2
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.
Connection Diagram
Product Variants
0335-01 - 335 ATS CONTROLLER 12V / 24V