Automatic Transfer Switch Control Modules

DSE705

Auto Transfer Switch Control Module

The DSE705 is an Automatic Transfer Switch Control Module for use with generator applications. The module monitors an incoming mains (utility) supply and issues a start command to the generator control system when the power fails.   

When the generator is producing the required output the DSE705 switches the load from the mains (utility) supply. When the mains (utility) supply returns the DSE705 switches the load back. The generator is instructed to cool down and stop.  

Read More
OVERALL SIZE
165 mm x 125 mm x 29 mm (6.5” x 4.9” x 1.2”)
PANEL CUTOUT SIZE
149 mm x 109 mm (5.9” x 4.3”)
MAXIMUM PANEL THICKNESS
8.0mm (0.3”)
WEIGHT
0.22kg
PRODUCT VARIANTS
0705-00 - 705 Auto Transfer Switch Control Module 

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery County/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features & Benefits

Key Features

Key Benefits

Automatic mains (utility) supply monitoring.
No requirement for an external detection relay.
Load changeover control.
Automatic changeover removes the need for user intervention.
Manual start function.
Convenient for system testing.
Automatic switch over between supplies.
Provides fast switching with no contact wear.
Single/three phase mains (utility) sensing.
Flexibility for single or three phase installations.
Remote start input.
Provide a changeover onto the genset from a remote location.
  • Additional Features
  • Front panel mounting.
  • Front panel programming.
  • LED indicators.
  • Configurable timers.
  •  

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries.

MAXIMUM OPERATING CURRENT
50mA

MAXIMUM STANDBY CURRENT
50mA

ALTERNATOR INPUT RANGE
75V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY
50Hz – 60Hz at rated engine speed (Minimum: 75V AC L-N)

OUTPUTS

START & RUN OUTPUTS
1.2 Amp DC at supply voltage. Switches to battery negative when active

CLOSE GEN/MAINS (UTILITY) CONTROL OUTPUTS
1.2 Amp DC at supply voltage. Switches to battery negative when active

AUXILIARY OUTPUTS
1.2 Amp DC at supply voltage. Switches to battery negative when active

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.

Connection Diagram

DSE705 connection diagram

Product Variants

 0705-00 - 705 ATS MODULE WITH DSE LOGO