DSE2160 (DSEM-Series)
DSENet® Input / Output Expansion Module (DSEM-Series)
Request a Quote
Product Highlights
Key Features
Specification
8 V to 35 DC Continuous
CRANKING DROPOUTS
Survives 0 V for 50 ms, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs are not maintained during cranking.
MAXIMUM OPERATING CURRENT
190 mA at 12 V, 90 mA at 24 V
MAXIMUM STANDBY CURRENT
34 mA at 12 V, 20 mA at 24 V
DIMENSIONS (W x H x D)
120 mm x 75 mm x 31.5 mm / 4.72” x 2.95” x 1.24”
Environmental Testing Standards
BS EN 61000-6-2 - EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4 - EMC Generic Emission Standard for the Industrial Environment
Electrical Safety
BS EN 61010 - Safety of Information Technology Equipment, including Electrical Business Equipment
Temperature
BS EN 60068-2-1 - Ab/Ae Cold Test -30°C
BS EN 60068-2-2 - Bb/Be Dry Heat +70°C
Vibration
BS EN 60068-2-6 - Ten sweeps in each of three major axes
5Hz to 8 Hz at +/-7.5mm
8Hz to 500 Hz at 2gn
BS EN 60068-2-30 - Db Damp Heat Cyclic 20/55°C at 95% RH 48 Hours
BS EN 60068-2-78 - Cab Damp Heat Static 40°C at 93% RH 48 Hours
Shock
BS EN 60068-2-27 - Three shocks in each of three major axes
15 gn in 11 ms
Degrees of Protection Provided by Enclosures
BS EN 60529 - IP21 - Front of module when installed into the control panel.