Digital Automatic Voltage Regulators (AVR)
DSEA109
Digital Automatic Voltage Regulator (AVR) with CAN Communications & PMG
The DSEA109 Digital Automatic Voltage Regulator (AVR) with CAN is designed to regulate the output voltage of an AC alternator. The DSEA109 is supplied by either a 3 phase PMG, single phase PMG, stator auxiliary winding or a shunt system taking power from the output windings.
The DSEA109 eliminates the complexities involved with analogue AVR designs. Analogue AVR designs can be over sensitive to changes in temperature which affects stability whereas the DSEA109 AVR maintains a smooth, stable regulated AC output voltage, regardless of the electrical load connected.The DSEA109 also features 3-phase sensing for better regulation.
Please Note: The DSE815 interface is required for programming.
The DSEA109 is simple to install and set up using either the DSE Configuration Suite PC Software and the DSE815 configuration interface or five onboard potentiometers and 4 DIP switches, combined with a status LED providing a simple user interface.
The DSEA109 Digital AVR has numerous advanced features such as a CAN port providing J1939 communications, soft start ramping, connection for a quadrature droop CT and the ability to perform remote voltage adjustment, making it perfect for synchronising and load sharing applications. The DSEA109 Digital AVR is an ideal option for both OEM and retro-fit solutions.
To view UL Certification click here. |
180 mm x 145 mm x 61 mm (7.0” x 5.7” x 2.4”)
WEIGHT
0.46 kg
PRODUCT VARIANTS
A109-01 - A109 Digital AVR With CAN Communications & PMG
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
POWER SUPPLY
VOLTAGE RANGE
100 V AC to 270 V AC (Ph to N & Ph to Ph)
FREQUENCY RANGE
40 Hz to 400 Hz
ALTERNATOR OUTPUT SENSING
VOLTAGE RANGE
15 V AC to 600 V AC (Ph to Ph & Ph to N)
FREQUENCY RANGE
40 Hz to 65 Hz
EXCITATION OUTPUT
EXCITER FIELD WINDING IMPEDANCE
5 Ω to 50 Ω
CONTINUOUS VOLTAGE RATING
0 V DC to 100 V DC
CONTINUOUS CURRENT RATING
0 A DC to 7 A DC
MAXIMUM CURRENT RATING
15 A DC for 10 seconds
QUADRATURE DROOP CT
MAXIMUM SECONDARY CURRENT
5 A AC
BURDEN
0.25 VA
ACCURACY
1%
REMOTE VOLTAGE ADJUSTMENT
POTENTIOMETER
5 kΩ
VOLTAGE INPUT
-10 V DC to 10 V DC
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.