Expansion Modules
DSE2131
DSENet® Ratiometric Input (10) Expansion Module
The DSE2131 is a ratiometric input expansion module providing 10 additional inputs to the control module. Up to 4 x DSE2131 modules can be linked together to provide up to 40 additional inputs.
Designed to give greater input flexibility for meeting complex industry generator control specifications.
Inputs can be configured to connect to resistive sensors, 0-10 V DC signals or 4-20mA signals, analogue inputs. All configurations are controlled from within the host control module.
To view UL Certification click here.
165 mm x 76 mm x 49 mm (6.5” x 3.0” x 1.9”)
WEIGHT
0.22kg
PRODUCT VARIANTS
2131-01 - 2131 Ratiometric Input Expansion Module
Request a Quote
Product Highlights
Key Features
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8V to 35V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
292 mA at 12 V, 167 mA at 24 V
101 mA at 12 V, 66 mA at 24 V
INPUTS
10 inputs configurable for digital/resistive (3k ohms) 4-20 mA and 0-10 V DC
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
Connection Diagram
Product Variants
2131-01 - 2131 RATIOMETRIC DSENET MODULE