Expansion Modules

DSEG0123

Load Share Lines Interface

The DSEG0123 Analogue Load Share Lines Interface converts DSE AMSC / MSC digital load share communications to universal analogue load share lines, allowing DSE paralleling controllers to seamlessly deliver kW and kvar load sharing with third party manufactured products. The DSEG0123 also allows the DSEG8600, DSEG8900, DSE8610 MKII, DSE8610, DSE7510 and DSE5510 controllers to be added to an existing DSE load sharing application and deliver kW and kvar load sharing across all DSE controllers within the system. The flexibility of the DSEG0123 makes expanding existing systems extremely simple. 

OVERALL SIZE
164.5 mm x 76.4 mm x 48.9 mm (6.48” x 3.0” x 1.93”) 
WEIGHT
0.2kg
PRODUCT VARIANTS
G0123-01 - Analogue Loadshare Lines Interface

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery County/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features & Benefits

Key Features

Key Benefits

Converts a DSE MSC link to analogue load share lines.
Allows controllers to communicate with controllers of a different type or manufacturer.
Compatible with multiple manufacturers paralleling controllers.
Ultimate flexibility across a wide range of existing applications.
Configuration Suite PC software configuration.
Intuitive user programming using the standard DSE software platform.
PC SCADA instrumentation for system diagnostics.
Provides detailed monitoring information.
Power on / status LEDs.
Easily view what mode the product is in.
USB programming port.
Provides simple universal connection.

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V DC Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.

MAXIMUM OPERATING CURRENT
150 mA at 12 V, 80 mA at 24 V

MAXIMUM STANDBY CURRENT
150 mA at 12 V, 80 mA at 24 V

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.

Product Variants

 G0123-01 - ANALOGUE LOADSHARE LINES INTERFACE