Load Sharing & Synchronising Control Modules
DSE8810
Load Share Control with Graphical Colour Display
The DSE8810 is an intelligent graphical colour display load share control module packed with industry leading features to enhance multi-set control. The module can be synchronised with up to 32 generators within the same system.
245 mm x 184 mm x 50 mm (9.6” x 7.2” x 2.0”)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7" x 6.3")
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.98kg
PRODUCT VARIANTS
8810-01 - 8810 Load Share Control Module with Graphical Colour Display
Request a Quote
Product Highlights
Key Features
Key Benefits
- Additional Features
- R.O.C.O.F & vector shift.
- Generator load demand.
- Automatic hours run balancing.
- Bus failure detection.
- Electrical protections.
- Modbus RTU/TCP support.
- Configurable display languages.
- Audible alarms.
- Engine protections.
- Flexible sender inputs.
- Configurable timers & alarms.
- Configurable maintenance alarms (3).
- Multiple date & time scheduler.
- CANbus for electronic engines.
- Comprehensive fuel monitoring.
- Backed-up real time clock.
- SMS messaging start & stop functionality.
- Modem diagnostic tool.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
600 mA at 12 V, 300 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (CRANK)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E TO L
2 A DC at supply voltage
GENERATOR & BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
BUILT-IN GOVERNOR CONTROL
MINIMUM LOAD IMPEDANCE1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated
BUILT-IN AVR CONTROL
MINIMUM LOAD IMPEDANCE1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.
Connection Diagram
Product Variants
8810-01 - 8810 COLOUR AUTO START LOAD SHARE CONTROLLER