Load Sharing & Synchronising Control Modules
DSE8920
7" Colour Load Share & Synchronising Control Module
OVERALL SIZE
310 mm x 162 mm x 51 mm (12.2" x 6.4" x 2.0")
PANEL CUTOUT SIZE
282 mm x 136 mm (11.1" x 5.4")
MAXIMUM PANEL THICKNESS
8.0 mm (0.3")
WEIGHT
1.0 kg
PRODUCT VARIANTS
8920-01 - 8910 7" Colour Load Share & Synchronising Control Module
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING5 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
1.2 A at 12 V 0.6 A at 24 V
MAXIMUM STANDBY CURRENT
0.7 A at 12 V, 0.35 A at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
INPUTS & OUTPUTS
DIGITAL INPUTS A TO LNegative Switching
ANALOGUE INPUTS A TO D
Configurable as:
Negative switching digital input
0 V to 10 V sensor
4 mA to 20 mA sensor
0 Ω to 480 Ω sensor
OUTPUTS A & B (FUEL & START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (volt-free)
AUXILIARY OUTPUTS E TO L
2 A DC at supply voltage
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
BUILT-IN AVR GOVERNOR CONTROL
MINIMUM LOAD IMPEDANCE
500 Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
0 V to 10 V DC
Fully isolated
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.