Manual & Auto Start Control Modules
DSE402MKII
Waterproof Manual & Auto Start Control Module
The DSE402 MKII is a waterproof Auto/Manual Start Control Module designed for generator and engine only applications. The intelligent design combines smart features with a waterproof key switch and enclosure to provide an excellent control option for wet/humid environments.
157 mm x 111 mm x 60 mm (6.2” x 4.4” x 2.4”)
Excludes Key Switch
PANEL CUTOUT SIZE
132 mm x 84 mm (5.2 " x 3.4")
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.45kg
PRODUCT VARIANTS
0402-03 - 402 MKII Waterproof Engine Control Module (Mpu)
0402-04 - 402 MKII Waterproof Engine Control Module (Hz)
0402-05 - 402 MKII Waterproof Engine Control Module with ETS (Mpu)
0402-06 - 402 MKII Waterproof Engine Control Module with ETS (Hz)
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
MAXIMUM OPERATING CURRENT
120 mA at 12 V, 170 mA at 24 V
TYPICAL OPERATING CURRENT
60 mA at 12 V, 75 mA at 24 V In stop position consumption is zero.
CHARGE/FAIL EXCITATION RANGE
0 V to 35 V
OUTPUTS
FUEL15 A DC at supply voltage
START
15 A DC at supply voltage
PRE-HEAT
2 A DC at supply voltage
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP66 - Front of module when installed into the control panel with the optional sealing gasket.
Connection Diagram
Product Variants
0402-03 - 402 MKII W/PROOF ENGINE CONTROLLER (MPU)
0402-04 - 402 MKII W/PROOF ENGINE CONTROLLER (HZ)
0402-05 - 402 MKII W/PROOF ENGINE CONTROLLER WITH ETS (MPU)
0402-06 - 402 MKII W/PROOF ENGINE CONTROLLER WITH ETS (HZ)