The DSE702 is a compact control module with an hours counter display. The module offers a range of features for single-set applications including low oil pressure, high engine temperature and over speed monitoring.
84 mm x 72 mm x 34.9 mm (3.3" x 2.8" x 1.4")
PANEL CUT-OUT SIZE
80 mm x 68 mm (3.1" x 2.7')
MAXIMUM PANEL THICKNESS
8 mm (0.3")
WEIGHT
0.16kg
PRODUCT VARIANTS
0702-00 - 702 Auto Start Control Module (Hours Counter, DSE Logo)
0702-10 - 702 Manual Start Control Module (Hours Counter, DSE Logo)
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
OUTPUTS
CRANKSolid state 1.2 A negative grounding terminal
FUEL
Solid state 1.2 A negative grounding terminal
PRE-HEAT
Solid state 1.2 A negative grounding terminal
GENERATOR
VOLTAGE RANGE15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
Connection Diagram
Product Variants
0702-00 - 702 AUTO START WITH HOURS COUNT DSE LOGO
0702-10 - 702 MANUAL START HOURS COUNT DSE LOGO