Remote Communications & Overview Displays
DSE855
USB to Ethernet Communications Device
The DSE855 communications device allows monitoring of a single DSE controller with USB connectivity over a LAN or WAN connection. To achieve this the DSE855 utilises its in-built web server or MODBUS TCP. In order to use over a LAN connection the on-site router must be configured to be accessible from any global location.
Works with:
Auto Start:
DSEL401MKII/DSE4310/DSE4410/DSE4510/DSE4610/DSE6010 MKII/DSE6110/DSE6610/DSE7110 MKII/DSE7210/DSE7310
Auto
Mains (Utility) Failure:
DSE4320/DSE4420/DSE4520/DSE4620/DSE6020/DSE6120 MKII/DSE6620/DSE7120MKII/DSE7220/DSE7320
35 mm x 97 mm x 102 mm (1.4” x 3.8” x 4.0”)
WEIGHT
0.16kg
PRODUCT VARIANTS
0855-01 - 855 USB to Ethernet Communications Device
Request a Quote
Product Highlights
Key Features
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
123 mA at 12 V
71 mA at 24 V
MAXIMUM STANDBY CURRENT
104 mA at 12 V
63 mA at 24 V
COMMUNICATIONS
USB (Single DSE Controller)
Ethernet
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.
Connection Diagram
Product Variants
0855-01 - 0855 USB TO ETHERNET MODULE