12 Volt Battery Chargers
DSE9460
12/24 volt 5 amp Enclosed Intelligent Battery Charger
The DSE9460 is an intelligent enclosed battery charger that has been developed to offer the highest levels of safety, usability and battery life and performance. The charger can be used straight out of the box or connected to a PC via a USB cable to modify the pre-set charging curves. The charging curve can be selected from the PC software or user created for advanced battery applications.
The charger can be used as a power supply and includes a high number of input/output protections as standard. The charger also has the ability to connect to an external system via MODBUS RTU, using RS485.
165 mm x 305 mm x 110 mm (6.5” x 12.0” x 4.3”)
WEIGHT
2.3kg
PRODUCT VARIANTS
9460-01 - 12 volt 5 amp Enclosed Intelligent Battery Charger (Display)
9460-02 - 12 volt 5 amp Enclosed Intelligent Battery Charger (Display & Meters)
9460-11 - 24 volt 5 amp Enclosed Intelligent Battery Charger (Display)
9460-12 - 24 volt 5 amp Enclosed Intelligent Battery Charger (Display & Meters)
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
AC SUPPLY
VOLTAGE RANGE
90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT RATING
5 A DC at 12 & 24 V DC
RIPPLE AND NOISE
<1%
EFFICIENCY
>86%
AUXILIARY OUTPUT
100 mA DC at 12 V
REGULATION
LINE
<0.5%
LOAD
2%
TEMPERATURE SENSOR INPUT
PT1000
PROTECTIONS
Short Circuit
DC Over Voltage
DC Over Current
Reverse Polarity
Over Temperature
AC Under & Over Voltage
Battery Charger Failure
CHARGE FAILURE RELAY
3 A at 30 V DC volt-free relay
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
Connection Diagram
Product Variants
9460-01 - 12V 5A ENCL BC + DISPLAY
9460-02 - 12V 5A ENCL BC DISPLAY + MTRS
9460-11 - 24V 5A ENCL BC + DISPLAY
9460-12 - 24V 5A ENCL BC DISPLAY + MTRS